- GICC FAQ |
- Disclaimer |
»
Frequently Asked Questions (Please
read
the Disclaimer for the FAQ's.) Click on the topic
below.
Adoption Year of Consumer Product Safety Commission (CPSC) 16 CFR 1201
Q: In what year did the Consumer
Product Safety Commission (CPSC) standard on safety glazing
become effective?
A: The CPSC standard, 16 CFR 1201, became
effective July 6, 1977.
Q: What is the definition of Safety Glazing?
A: Any glazing that has passed either test CPSC 16 CFR 1201 for Category I or II or ANSI Z97.1-2004 for Class A
or B.
Q: How can glass be designed for use in floors?
A: At this time there is no reference to
glazing in floors in the model building codes, there is an ASTM
International standard practice in development, please consult a
structural engineer.
Glazing in Skylights or Sloped Glazing
Q: Is there a minimum thickness of interlayer that is
required for laminated glass used in skylights?
A: The International Building Code (IBC)
requires laminated glass used in skylights or sloped glazing to have
a minimum 0.030 inch interlayer, except in residential applications
covered by the International Residential Code (IRC) where laminated
glass used in skylights, with a surface area less than 16 square
feet and located 12 feet or less above a walking surface is
permitted to have a 0.015 inch interlayer. Since this exception is
relatively new, check with the state or local jurisdiction to see if
this model code provision has been adopted.
Q1: Is decorative glazing in doors required to be safety
glazing?
A: Glazing in doors is addressed by CPSC 16
CFR 1201 which contains a limited exception from the safety glazing
requirements meeting the criteria in Section 1201(c)(4). For other
applications, the International Building Code (IBC) also contains an
exception for decorative glass (see Section 2406.3.1, IBC 2006).
Q2: Is there a minimum fire protection
rating for glazing in the door leaf of doors?
A: Glazing installed in the door leaf of
fire doors is required to have a fire protection rating that matches
the rating of the door. Fire door ratings range from 20-minutes to 3
hours.
Q3: Do overhead garage doors require safety
glazing?
A: The Federal Safety Standard, CPSC 16 CFR
1201 does not apply to garage doors designed for vehicular passage,
but glazing material in doors of garages designed solely for human
passage is included within the scope of CPSC 16 CFR 1201 and
therefore, must satisfy the standard’s safety criteria. Glass in a
sectional garage door does not require safety glazing.
Glazing in and around Elevators and Escalators
Q1: What are the glazing requirements for elevator
enclosures?
A: According to Section 100, Construction
of Hoistways and Hoistway Enclosures of ANSI A17, laminated glass
meeting the requirements of ANSI Z97.1-2004 or CPSC 16 CFR 1201 is
required. Each lite of glass must be labeled according to the
requirements of ANSI Z97.1-2004; and the label shall be visible
after installation. There are currently proposals to make changes to
this requirement.
Q2: Are there model code requirements on
glass in escalator handrails?
A: Yes, section 2407 of the International
Building Code (IBC), 2006 Edition, states that glass in railings
shall be either monolithic fully tempered glass, laminated fully
tempered glass or laminated heat-strengthened glass. The minimum
nominal thickness shall be ¼” and the glass is to comply with the
safety glazing Category II requirements of CPSC 16 CFR 1201.
Glazing around Swimming Pools and Whirlpool Enclosures
Q1: What are the requirements for safety glazing in the
vicinity of swimming pools?
A: The International Building Code (IBC)
section 2406.3(9) prescribes safety glazing for all glazing within
60 inches of the floor and within 60 inches horizontally of the
water’s edge. Please consult the local building official for the
required safety glazing criteria in your area.
Q2: When glazing forms an enclosure for a
whirlpool in a single-family dwelling, what are the requirements?
A: Glazing in doors and enclosures for
whirlpools shall comply with CPSC 16 CFR 1201 Category II. If the
glazing is in the wall that forms the enclosure and it is less than
60 inches above the standing surface it shall comply with CPSC 16
CFR 1201 Category II or ANSI Z97.1-2004 Class A.
Q1: What are the test requirements for a 20-minute
fire-rated door?
A: According to the definitions found in
Chapter 7 of the International Building Code (IBC), a fire door is
the door component of a fire door assembly. A fire door assembly is
any combination of a fire door, frame, hardware, and other
accessories that together provide a specific degree of fire
protection to the opening. Glazing in the door leaf shall be tested
in accordance with National Fire Protection Association (NFPA) 252.
Check with the local building code official regarding hose stream
testing requirements.
Q2: What is the difference between a fire
door and a fire door assembly, and related areas where fire-rated
glazing may be required?
A: The 2007 Edition of the National Fire
Protection Association (NFPA) 80 – Standard for Fire Doors and Other
Opening Protectives provides the following definitions:
1. Fire door. The door component of a
fire door assembly. |
Q3: Does the International Building Code
(IBC), require a hose stream test for fire-rated glazing?
A: Yes, with the exception of glass lites
installed in the door leaf of doors required to have a fire
protection rating of 20 minutes or less.
Q4: What is required for glazing to meet
Category II of CPSC 16 CFR 1201 for an athletic facility?
A: To meet CPSC 16 CFR 1201 Category II (or
ANSI Z97.1-2004 Class A), it must not break at all or break safely
when impacted at 400 ft-lbs force from a 100 lb lead shot filled
bag. The impact performance is satisfactory if the glass breaks and
the impact creates small enough particles of glass for tempered
lites and no penetration large enough for a 3” solid sphere placed
on the opening for laminated to pass through freely. There may be
additional requirements on structural and glazing technique for an
athletic facility in the building code.
Q5: What are restrictions associated with
the use of wired glass?
A: In the past, model building codes have
provided an exception for wired glass installed in locations
requiring fire-rated glass. However, the 2006 Edition of the
International Building Code (IBC) no longer contains the exception.
If wired glass is installed in a hazardous location, it must meet
the applicable safety glazing requirements. If the wired glass is
installed in a location that is not a hazardous location, the wired
glass need only meet the applicable fire protection requirements.
Q1: Can etched tempered glass and etched laminated glass be
used as safety glazing?
A: Etched tempered glass and etched
laminated glass can be used as safety glazing if they comply with CPSC 16 CFR 1201 and/or ANSI Z97.1-2004.
Q2: Is decorative glazing in doors required
to be safety glazing?
A: Glazing in doors is addressed by CPSC 16
CFR 1201 which contains a limited exception from the safety glazing
requirements meeting the criteria in Section 1201(c)(4). For other
applications, the International Building Code (IBC) also contains an
exception for decorative glass (see Section 2406.3.1, IBC 2006).
Q: What is the deflection requirement of interior
butt-glazed areas installed adjacent to a walking surface?
A: According to the International Building
Code (IBC) Section 2403.4, the differential deflection of two
adjacent unsupported edges, such as the type of glass installed in
shopping mall storefronts, shall not exceed the thickness of the
panels when a force of 50 lbs. per linear foot is applied
horizontally to one panel at any point up to 42” above the walking
surface.
Q: Is there a section in the International Building Code
(IBC) that deals with the proper mounting of frameless mirrors and
are there any code requirements?
A: According to the International Building
Code (IBC) Section 2406.3.1 item 7, mirrors that are mounted in
positions exposed to human impact (i.e., hazardous locations as
defined in the IBC) must be safety glazing. The IBC contains an
exception for “mirrors and other glass panels mounted or hung on a
surface that provides continuous backing support.”
Q1: What is required for glazing to meet Category II of CPSC
16 CFR 1201 for an athletic facility?
A: To meet CPSC 16 CFR 1201 Cat II (or ANSI
Z97.1-2004 Class A),it must not break at all or break safely when
impacted at 400 ft-lbs force from a 100 lb lead shot filled bag. The
impact performance is satisfactory if the glass breaks and the
impact creates small enough particles of glass for tempered lites
and no penetration large enough for a 3” solid sphere placed on the
opening for laminated to pass through. There may be additional
requirements on structural and glazing technique for an athletic
facility n the building code.
Q2: What are restrictions associated with
the use of wired-glass?
A: In the past, model building codes have
provided an exception for wired glass installed in locations
requiring fire protection rated glass. However, the 2006 Edition of
the International Building Code (IBC) no longer contains the
exception. If wired glass is installed in a hazardous location, it
must meet the applicable safety glazing requirements. If the wired
glass is installed in a location that is not a hazardous location,
the wired glass need only meet the applicable fire protection
requirements.
Q1: What are the major energy codes?
A: Energy code requirements vary by
location, but are generally based on one of three model codes or
standards: the American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE) 90.1, the International Energy
Conservation Code (IECC), or the International Residential Code
(IRC).
ASHRAE 90.1 is the energy standard most often used for commercial buildings and for residential buildings over three stories. The IECC includes different chapters for low-rise residential buildings (three stories or less) and commercial buildings (including high-rise residential buildings). The IRC includes requirements for low-rise one and two-family homes and townhouses. The IECC and IRC have very similar requirements up through the 2006 version, and both are widely used for low-rise one and two family homes and townhouses.
A few jurisdictions have their own energy codes which differ from ASHRAE 90.1, IECC, and IRC, most notably California, Florida, Oregon, and Washington.
Each model energy code has prescriptive requirements for the U-factor, Solar Heat Gain Coefficient (SHGC), and air leakage of fenestration products, based upon climate zone, building type, and product type. ASHRAE 90.1, IECC, and IRC all use the same 8 climate zones as shown below:

Q2: Where is low-e glass required?
A: Basically everywhere, or at least where
the most recent energy code has been adopted and is enforced. The
exact prescriptive requirements vary depending on which version of ASHRAE 90.1, IECC, or IRC is being enforced in a particular
location. For the latest versions (ASHRAE 90.1-2007, 2006 IECC, and
2006 IRC), low-e is essentially required in all climate zones. In
the north, the low U-factor necessitates the use of low-e, as well
as good frames, and possibly argon gas fill. In the south, the low
Solar Heat Gain Coefficient (SHGC) requires glazing with a tint,
reflective coating, or spectrally selective low-e coating. Because
of the recent increased demand for high light transmittance and
daylighting, this has meant the increased use of low-e.
Q3: Where is double glazing required?
A: With the latest versions of the model
energy codes, double glazing is required everywhere except zone 1
(just the southern tip of Florida, Hawaii, Puerto Rico, and the
Virgin Islands). The exact prescriptive requirements vary depending
on which version of ASHRAE 90.1, IECC, or IRC is being enforced in a
particular location. For the latest versions (ASHRAE 90.1-2007, 2006
IECC, and 2006 IRC), the prescriptive U-factor requires double
glazing in all climate zones except zone 1. However, single glazing
may still be used if an alternate trade-off method is used (refer to
Q5 for information on trade-off methods).
Q4: Are the code requirements for center-of-glazing
or whole product? What’s the difference?
A: All U-factor, Solar Heat Gain
Coefficient (SHGC), and Visible Transmittance (VT) requirements in
ASHRAE 90.1, IECC, and IRC are whole product values, meaning that
the effect of the frame is included along with the glazing. Because
the frame is opaque, the whole product VT will always be lower than
the center-of-glazing value. For U-factor and SHGC, the difference
depends upon the relative amount of glazing vs. frame area, as well
as the different glazing and frame materials. In general, center-of-glazing
values are not accepted for code compliance. The one exception is
that ASHRAE 90.1 allows the center-of-glazing SHGC as an alternative
for complying with the whole product SHGC (refer to Q7 for more
information on exceptions).
Q5: Are there options besides the basic
prescriptive requirements for U-factor and SHGC?
A: Yes. All model energy codes generally
have three different ways to comply. The first is simply to meet the
prescribed U-factor and SHGC values for your climate zone and
application. The second is a simplified trade-off where lower
performance in one envelope component can be offset by higher
performance in another – for example, area-weighting across
different window types, or trading off a higher glazing U-factor for
increased wall insulation. The third is a complete building
performance simulation where any change in the building is allowed
as long as the overall proposed building has the same or lower
energy cost as a hypothetical reference building meeting the
prescriptive requirements. This third option is the most complex,
but also allows the most flexibility, with the ability to trade-off
performance between different building components, HVAC equipment,
etc.
Q6: What are the rating and labeling
requirements for glazing in the energy codes?
A: It depends. There are no labeling
requirements if the glazing either uses conservative, worst-case
default values for U-Factor and SHGC, or falls under certain
exemptions. More information about default values and exemptions is
provided in Q7 below.
Otherwise, the IECC, IRC, and ASHRAE 90.1 all require that the U-factor and SHGC be determined by an accredited, independent laboratory in accordance with NFRC technical procedures (NFRC 100 and 200). However, although the manufacturer or glazing contractor must follow NFRC technical procedures and use an accredited independent laboratory, only a few places such as California and Washington require use of the full NFRC certification program including registration with NFRC, additional review by an Independent Certification and Inspection Agency (IA), and fee payment.
For commercial glazing, some manufacturers also rate their products using AAMA 507, which is an alternative rating standard still based on NFRC technical procedures but more suited to the custom nature of the commercial glazing industry. Not all jurisdictions accept this alternative rating system. Although an actual individual label is common for residential windows, certificates listing installed products on a building are more common than labels for commercial projects.
Q7: What exceptions are there to rating, labeling, and meeting the U-factor and SHGC requirements?
A: First, even if a product does not fall
under one of the following exceptions, each model code allows the
use of default U-factor and SHGC values for unlabeled products. The
exact value depends on the code, the framing type, and the glazing
type. However, in each case, the default values are designed to be
conservative, worst-case values, and often will not meet the
prescriptive requirements. Therefore, default values are usually
only used when an alternative trade-off method is being used (refer
to Q5 for more information on trade-off methods).
Several exemptions or exceptions to U-factor and SHGC requirements are listed below:
1) For low-rise residential buildings, the
IECC and IRC allow 15 ft2 of a glazing area per dwelling unit to be
exempt from all U-factor and SHGC requirements. |
Q8: What is a projection factor, and how
does that affect glazing code compliance?
A: The projection factor (PF) is a measure
used to describe how well an overhang shades glazing, and is
important when determining code compliance with SHGC requirements.
Projection factor is calculated as the furthest horizontal distance
out away from the glazing surface, divided by the distance from the
bottom of the glazing to the bottom of the overhang. For example, a
2 ft overhang offset 1 ft above a 5 ft high window would have a PF =
2 / (5+1) = 0.33.
For commercial glazing, both ASHRAE 90.1 and IECC give credit towards meeting the SHGC requirement for using overhangs. In the IECC, higher SHGC values are allowed based on projection factors less than 0.25, between 0.25 and 0.50, and higher than 0.50. In ASHRAE 90.1, the SHGC used for compliance is determined by reducing the actual product SHGC by a multiplier based on the projection factor and the direction the glazing faces. ASHRAE 90.1 also includes a procedure for calculating the effectiveness of partially opaque overhangs (e.g. using translucent materials, perforated materials, or louvers). The effective SHGC is reduced more for larger overhangs, and for more opaque materials.
